Limit value monitoring_6003614_Standard Module

MCR-PSP-DC - Limit Value Switch, Programmable

For process monitoring and control
Permanent reading display
Four separately configurable switching thresholds
For thermoelement sensors, resistance thermometer and linear resistances
Two relay outputs with changer contact and configurable delay
Electrically isolated input signals
Programmable with MCR-CONF software

Measuring input  
Input signal:  
Resistance
thermometer:
2, 3 or 4 cable technology to IEC 751/DIN IEC 751 or SAMA RC 21-4:1966: e.g. Pt100, Ni etc.
Resistance: 0 to 8kΩ (2-cable circuit only)
Thermoelement
sensors:
(B, E, J, K, L, N, R, S, T, U) to
IEC 584-1/DIN 43 710
Voltage: -30V to +30V
Current: -30mA to +30mA
Input resistance: Current: 50Ω/ Voltage: 200kΩ
Setting accuracy: 0.1°C/0.01V/0.01mA/0.1Ω
Input
protection:
Transient protection, surge-proof to 30V DC
Measuring output  
Relay stage: 2 x changer contacts/ sloping/attracting (reversible) per 2 switching points
Contact material: AgNiO 0,15 + HTV (hard gold-plated)
Max. switching voltage 250V AC
Max. Continuous current: 2 A
Status display: 5-character, 7-segment display and LEDs
Display resolution: 0.1°C/0.01V/0.01mA/0.1Ω
Response delay: 0 to 2s, configurable
General data  
Supply voltage: 20 to 30V DC
Power consumption: <60mA
Test voltage,  
Auxiliary energy/input: 1kV, 50Hz,1min
Temperature coefficient: ≤0.01%/K
Ambient  
temperature range: -20°C to +65°C
Standards/
Conditions:
IEC 664/IEC 664 A/DIN
VDE 0110-1:1989-01
Electromagnetic
compatibility:
CE-compliant for EMC Directive
89/336/EEC
- Radiated interference: EN 50 081-2
- Interference immunity EN 50 082-2